• Tel:86-510-86281566
  • 86-510-80620298
  • Fax:86-510-80629077

XDG3212G vibration monitor

XDG3212G vibration monitor

The absolute vibration of large rotating machinery such as steam turbines, water turbines, generators, compressors, fans and pumps shall be monitored and protected.


Overview

The vibration monitor is mainly used in power generation, steel, metallurgy, chemical industry and other fields to continuously monitor and measure the bearing vibration (absolute vibration) of various rotating machinery, so that users can analyze and maintain the working conditions of the machine. The instrument is equipped with 4~20mA current, relay switching output, RS485 interface MODBUS-RTU communication protocol, which can easily form an automatic control system and monitoring protection system with DCS, PLC, PC, etc; The instrument adopts high-performance ARM processor and simultaneously monitors vibration amplitude and intensity. It has good stability, high accuracy, friendly and beautiful interface, simple operation, convenient and reliable maintenance, and is at the leading level in China.

Our product portfolio

  • 1. The vibration monitor takes the advanced ARM high-performance embedded processor as the core, and adopts professional signal conditioning and filtering circuits. The linearity, frequency response, temperature drift and anti-interference ability of the instrument measurement have been greatly improved, making the system measurement accuracy higher and the protection action more reliable

    2. It can simultaneously monitor the vibration value and intensity value of rotating machinery. (Relay alarm value and current output value correspond to main measurement parameters)

    3. The configuration mode is flexible, and the working mode and parameters of the instrument can be configured and set by the upper computer software configuration or by pressing keys and touch screen

    4. Dual channels can work independently or single channel can be used through configuration instrument

    5. The parameters of the instrument can be viewed or set locally. Including: meter number, baud rate, calibration mode, channel status, small signal removal, alarm reset mode, range, alarm set value (alarm I value, alarm II value), alarm delay value, (4~20) mA corresponding range, etc

    6. Peak memory and setting parameters can be stored for a long time after power failure

    7. It has power-on and power-off suppression function (protection of historical data, suppression of false alarm), and self-locking alarm output function within about 5 seconds after power-on

    8. RS485 communication interface and general MODBUS-RTU communication protocol realize the network communication and remote control functions of the instrument

    9. Sensor raw signal output

  • 1. Input: input two magnetoelectric speed sensors or two piezoelectric speed sensors at the same time

    2. Display range: vibration value up to 999µ m; The maximum intensity value is 99.9mm/s

    3. Range: vibration: (0~500)µ Any within m, error: full range± 1.0%。 Intensity: any within (0~50.0) mm/s, error: full range± 1.0%。

    4. Display mode: 3.5 inch TFT true color touch screen or digital tube

    5. Frequency response error: 10~1000Hz&le& plusmn; 10%

    6. Current output: (4~20) mA, independent for each channel, short circuit protection, maximum load 400Ω, Error:± of full scale; 1.0%。

    7. Alarm: alarm setting: 2 points per channel (alarm I, alarm II). Setting range: any setting within the full range. Alarm delay: any integer within the range of (0~30) seconds. Alarm output: relay normally open and normally closed contact mode output, contact capacity DC28V/2A or AC250V/1A

    8. Communication: RS485 communication interface, MODBUS-RTU communication protocol: baud rate: 4800bps, 9600bps (default), 19200bps, three options. Verification method: no verification (default), even verification and odd verification. Three options are available

    9. Environmental restriction: there is no corrosive and strong magnetic field around

    10. Temperature and humidity: operating temperature: (0~50) ℃. Limit temperature: (- 10~60) ℃. Storage temperature: (- 40~70) ℃. Relative humidity: (20~90)% RH (non condensing)

    11. Power supply: voltage (85~265) VAC, frequency 50Hz/60Hz, power consumption < 10W

    12. Instrument size and installation: overall dimension: width 160 mm× Height 80 mm× 130mm deep. Hole size: width 152 mm× 76mm high. Installation method: fixed on disk


Product Resources